For Engineers and Contractors
Technical Resources
Controller specifications, panel and wiring diagrams and gas sensor data for NES Custom Solutions and Plug & Play systems.
Controllers
Controller Specifications
NES 8000 Series
Standalone controller for small to mid-size garages with no BMS/EMS. Optional 10” panel-mounted display.
NES 9000 Series
For larger properties with existing building management infrastructure. Three versions: 9000, 9000X and 9000+.
Diagrams
Panel and Wiring Diagrams
The NES 9000+ uses the NES 9000 diagrams.
Model 8700
NES 8000 Series · PDF
Model 9000
NES 9000 Series also 9000+ · PDF
Model 9000X
NES 9000 Series · PDF
Sensors
Gas Sensors
NES Series 400 Dual Combined Gas Monitor
Carbon monoxide (CO) and nitrogen dioxide (NO2)
The NES Series 400 can serve as a single or dual 24V detector with RS-485 BACnet MS/TP or Modbus RTU communications, offering exceptional functionality, reliability and precision. Engineers can customize its settings on-site to fit project needs, monitoring one gas or two simultaneously, which reduces hardware and simplifies the controls work needed to achieve the sequence of operations.
It senses carbon monoxide (CO) and nitrogen dioxide (NO2) in commercial and industrial applications such as parking structures, engine repair shops, tunnels, equipment rooms and ventilation systems, and transmits readings to the NES central controller.
KEY FEATURES
- NFC app configuration
- Single or dual gas monitoring
- Replaceable, plug-and-play smart sensor modules
- Non-intrusive calibration
- Splash guard accessories for improved IP rating
- Modbus RTU or BACnet MS/TP (field selectable)
- 0–10V or 4–20mA output (field selectable)
- Relay output
- 24V AC/DC power supply
- Display screen and RGB LED status indication
- UL 2075 gas performance (CO and NO2)
- Supplied calibrated
- Strong anti-interference circuit boards; RoHS compliant
- Corrosion-resistant enclosure with optional accessories
- Indoor and outdoor use (with additional weatherproof sensor covers)
NES Series 300 CO Transmitter
Carbon monoxide (CO), RS-485
*For existing installations and replacements
The NES Series 300 Carbon Monoxide (CO) Transmitter monitors gas concentrations from gas-powered vehicles in underground parking garages and loading docks. It supports BACnet or Modbus® communication over RS-485 wire, so it works with almost any building management controller. Sensors can be field-calibrated with the optional A-449 remote LCD display, which also shows when a sensor needs replacement.
Drives
Variable Frequency Drives
Danfoss VLT® HVAC Drive FC 102
Sized to each fan motor
NES systems are bundled with Danfoss FC 102 HVAC drives, sized to each fan motor and controlled by the NES controller over native BACnet. Standard features include automatic energy optimization and integrated EMC/RFI filters. Drives are supplied in NEMA 12 enclosures with an internal disconnect; bypass is optional.
Alarms
Horn and Strobe Alarms
Edwards 6536-G5 Horn & Strobe
Audible and visual alarm, UL 1638 listed
The horn sounds when gas concentrations reach alarm levels, and the strobe signals a system fault, such as a drive going offline. The unit produces 82 dB at 10 feet with a 50-candela strobe, runs on 24V AC or DC and installs in a single-gang 2″ x 4″ box.
Research
Peer-Reviewed Research
Assessing Ventilation Control Strategies in Underground Parking Garages
Building Simulation, 2020 (Illinois Institute of Technology)
An Illinois Institute of Technology study comparing garage ventilation strategies found that linear DCV uses 84% less energy than standard variable flow (SVF) systems and 73% less than on/off systems.
Ready to Size Your System?
Call or email with your fan schedule and garage layout, and NES will recommend the right controller and quote the system. NES quotes cover equipment, engineering, installation and startup.